DocumentCode :
1173768
Title :
Guidelines For Determining Parallel Resonance On EHV Transmission Lines
Author :
Reid, W.E. ; Gustin, R.F. ; Zylstra, P.V.
Author_Institution :
McGraw-Edison Company Power Systems Division
Issue :
9
fYear :
1983
Firstpage :
3196
Lastpage :
3204
Abstract :
Generalized curves are derived which allow the utility engineer to easily determine the possibility of parallel resonance on EHV transmission lines. The curves are given for transposed and untransposed multi-circuit lines and for single-circuit lines where the misoperation of a single phase of a circuit breaker is to be considered. The parallel resonance problems associated with typical reactor and transformer configurations are evaluated.
Keywords :
Distributed parameter circuits; Guidelines; IEEE members; Inductors; Power systems; Power transmission lines; RLC circuits; Resonance; Shunt (electrical); Transmission lines;