Title :
Dynamic Stabilizer On-Line Experience
Author :
Kimmel, D.S. ; Carter, M.P. ; Bednarek, J.H. ; Jones, W.H.
Author_Institution :
Westinghouse Electric Corporation
Abstract :
A brief description is presented of the Westinghouse Torsional Dynamic Stabilizer, which was developed primarily as a countermeasure to "torsional interaction" subsynchronous resonance. Two such systems were installed and commissioned at the San Juan Generating Station, Waterflow, New Mexico in July, 1980. This paper describes the maintenance procedures and operating experience to date of these two units. The only known instance of operation at the high level bias point of the Stabilizer appears to indicate that the unit helped to dampen a turbine-generator shaft oscillation transient.
Keywords :
Circuits; Control systems; Inductors; Maintenance; Power transformer insulation; Switches; Temperature control; Testing; Thyristors; Transducers;
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
DOI :
10.1109/TPAS.1984.318579