DocumentCode
1174051
Title
A New Digital Relay for Generator Protection against Asymmetrical Faults
Author
Usta, O. ; Bayrak, M. ; Redfern, M. A.
Author_Institution
Istanbul Technical University; Sakarya University, Turkey; University of Bath, Bath, U. K.
Volume
21
Issue
11
fYear
2001
Firstpage
58
Lastpage
58
Abstract
Under unbalanced conditions the three phase instantaneous power oscillates at twice the power system frequency. The magnitude of these oscillations can be used as a measure of the system unbalance. This article has introduced a new digital relaying algorithm designed to detect asymmetrical faults by monitoring the sinusoidal oscillations of the three phase instantaneous power measured at the generator terminal. Once an asymmetrical fault is detected, the algorithm checks the direction of the negative sequence-reactive power flow at the machine terminal to discriminate between internal and external faults. Power system test studies presented show that the new relay provides fast tripping for internal asymmetrical faults and back-up protection for external asymmetrical fault conditions.
Keywords
Algorithm design and analysis; Digital relays; Electrical fault detection; Fault detection; Frequency; Power system faults; Power system measurements; Power system protection; Power system relaying; Protective relaying; Digital relaying; asymmetrical faults; generator protection; unbalanced power component;
fLanguage
English
Journal_Title
Power Engineering Review, IEEE
Publisher
ieee
ISSN
0272-1724
Type
jour
DOI
10.1109/MPER.2001.4311160
Filename
4311160
Link To Document