DocumentCode
1174300
Title
A Method For Estimating The Sinusoidal Iron Losses Of A Transformer From Measurements Made With Distroted Voltage Waveforms
Author
Arseneau, R. ; Moore, W.J.M.
Author_Institution
National Research Council of Canada Division of Electrical Engineering
Issue
10
fYear
1984
Firstpage
2912
Lastpage
2918
Abstract
A method for estimating the sinusoidal iron losses of a transformer from measurements made under highly distorted voltage waveform conditions is proposed. No assumption of the hysteresis/eddy current loss division within the transformer is required. A maximum discrepancy of 2% between the corrected and actual sinusoidal measurements was obtained during the testing of a 50 kVA, 2400 V single phase transformer with voltage waveforts containing six zero crossings per period.
Keywords
Distortion measurement; Eddy current testing; Eddy currents; Equations; Hysteresis; Iron; Loss measurement; Phase transformers; Power transformers; Voltage;
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/TPAS.1984.318293