DocumentCode :
1174304
Title :
Phase-to-Ground and Phase-to-Phase Sparkover Characteristics of External Insulation at the Entrance of an UHV Substation
Author :
Yamagata, Yoshiki ; Oe, A. ; Miyake, K. ; Aihara, Y. ; Shindo, Takatoshi
Author_Institution :
Tokyo Electric Company; Central Research Institute of Electric Power Industry
Volume :
21
Issue :
11
fYear :
2001
Firstpage :
62
Lastpage :
63
Abstract :
For rational insulation design of an UHV substation, full-scale switching impulse tests of phase-to-ground (shielding ring-to-tower) and phase-to-phase (shielding ring-to-shielding ring) insulating clearance have been carried out in dry and wet conditions. In the tests, shielding rings that will be installed on bushings at actual UHV substations were used. The sparkover voltages depend on not only gap configurations but also the waveform of applied switching impulses; in other words, they show what we refer to as U-characteristics. Critical sparkover voltages are higher than those of rod-rod gaps by 20-25% in dry conditions and by 7-10% in wet conditions.
Keywords :
Costs; Dielectrics and electrical insulation; Impedance; Power system harmonics; Resonance; Steady-state; Substations; Switches; Testing; Voltage;
fLanguage :
English
Journal_Title :
Power Engineering Review, IEEE
Publisher :
ieee
ISSN :
0272-1724
Type :
jour
DOI :
10.1109/MPER.2001.4311185
Filename :
4311185
Link To Document :
بازگشت