DocumentCode :
1174553
Title :
Simulator Study of Multiterminal HVDC System With Small Parallel Tap and Weak AC Systems
Author :
Krishnayya, P.C.S. ; Lefebvre, S. ; Sood, V.K. ; Balu, N.J.
Author_Institution :
Institut de Recherche d´´Hydro-Québec (IREQ)
Issue :
10
fYear :
1984
Firstpage :
3125
Lastpage :
3132
Abstract :
The paper describes a simulator study of a four-terminal HVdc system with a small parallel tap and interconnected to an AC network with weak AC systems at the four dc terminals. The small tap is rated at 25% of the rating of the HVdc system and the effective short-circuit ratios at the dc terminals are in the range of 2.1 to 3.0. The study includes the transient performance of the dc system for various types of system disturbances, such as AC system faults, dc line faults, and commutation failure at the small inverter.
Keywords :
Centralized control; Control systems; HVDC transmission; Inverters; Power & Energy Society; Power system interconnection; Power system planning; Printing; Protection; Rectifiers;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9510
Type :
jour
DOI :
10.1109/TPAS.1984.318334
Filename :
4112420
Link To Document :
بازگشت