• DocumentCode
    1174835
  • Title

    A Time Domain Procedure for Locating Switched Capacitors in Power Distribution

  • Author

    Kim, Jung-Ho ; Grady, W. M. ; Arapostathis, Ari ; Soward, J. ; Bhatt, S. C.

  • Author_Institution
    The University of Texas at Austin, Austin, TX; TXU Electric, Fort Worth, TX; Electric Power Research Institute, Palo Alto, CA
  • Volume
    21
  • Issue
    12
  • fYear
    2001
  • Firstpage
    69
  • Lastpage
    69
  • Abstract
    This paper develops a method using transient voltage and current measurements at the substation to determine which capacitor in a multicapacitor feeder switched on to cause a measured transient. The procedure is based upon time-domain analysis where a backward Kalman filter estimates the initial voltage of all feeder capacitors, and those estimates indicate which capacitor switched. The result is an automated procedure that can help electric utilities determine if their capacitors are switching properly, and also help pinpoint the source of capacitor switching-related power quality problems.
  • Keywords
    Broadcasting; Corona; Degradation; Electromagnetic interference; Global Positioning System; Power capacitors; Power distribution; Power quality; Power system planning; Power system reliability; Power quality; backward Kalman filter; capacitor switching; switched capacitor estimation;
  • fLanguage
    English
  • Journal_Title
    Power Engineering Review, IEEE
  • Publisher
    ieee
  • ISSN
    0272-1724
  • Type

    jour

  • DOI
    10.1109/MPER.2001.4311237
  • Filename
    4311237