DocumentCode :
1174975
Title :
Failure Analysis Of Polymeric-Insulated Power Cable
Author :
Mintz, J.David
Author_Institution :
Ontario Hydro Electrical Research Division
Issue :
12
fYear :
1984
Firstpage :
3448
Lastpage :
3453
Abstract :
This paper presents the findings of a survey conducted in Ontario to elucidate the contributing factors in primary-distribution, power-cable failures. Water treeing, although important, was involved in fewer failures than expected. Although a sensitivity analysis, was precluded by insufficient data on installed plant, four cable parameters were identified as contributing to water treeing. Internal defects (inclusions) were more prevalent than expected. No examples of electrical treeing were found.
Keywords :
Cable insulation; Conductors; Dielectrics and electrical insulation; Failure analysis; Moisture; Polyethylene; Polymers; Power cable insulation; Power cables; Trees - insulation;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9510
Type :
jour
DOI :
10.1109/TPAS.1984.318347
Filename :
4112467