• DocumentCode
    1175423
  • Title

    Ampacity of Cable in Covered Tray

  • Author

    Engmann, Gary

  • Author_Institution
    Black & Veatch Consulting Engineers
  • Issue
    2
  • fYear
    1984
  • Firstpage
    345
  • Lastpage
    352
  • Abstract
    Solid tray covers are used in power generating station cable tray systems. The published literature contains little data about the effects of tray covers on cable operating temperatures, and the National Electrical Code provides limited guidance. An analytic method for determining the allowable ampacity of cable in covered tray is developed and presented. The results of an experiment with a solid tray cover are presented and compared with predicted values.
  • Keywords
    Communication cables; Conducting materials; Heat transfer; National electric code; Power cables; Power generation; Power system protection; Solids; Temperature; Thermal conductivity;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1984.318250
  • Filename
    4112518