• DocumentCode
    1175617
  • Title

    A Computer Study and Model Demonstration of Safety Ground Locations During High Voltage Line Maintenance

  • Author

    Cole, W.H. ; McDermott, T.E.

  • Author_Institution
    Florida Power and Light Company
  • Issue
    3
  • fYear
    1984
  • fDate
    3/1/1984 12:00:00 AM
  • Firstpage
    455
  • Lastpage
    462
  • Abstract
    A digital computer study was performed to help determine whether safety grounds should be placed at the work site or at adjacent towers. Literature reviews and approximate formulas were used in addition to detailed computer simulation. During an accidental line energization, single-phase, single-point grounding reduces phase-to-tower voltages, and on that basis is the prefered method, but measures must be taken to counteract the ground level step and touch potentials. After the study, a working three-phase transmission line model was constructed to help demonstrate the study results to linemen.
  • Keywords
    Computer simulation; Contact resistance; Electric resistance; Electric shock; Grounding; Immune system; Poles and towers; Power transmission lines; Safety; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1984.318723
  • Filename
    4112541