DocumentCode
1175617
Title
A Computer Study and Model Demonstration of Safety Ground Locations During High Voltage Line Maintenance
Author
Cole, W.H. ; McDermott, T.E.
Author_Institution
Florida Power and Light Company
Issue
3
fYear
1984
fDate
3/1/1984 12:00:00 AM
Firstpage
455
Lastpage
462
Abstract
A digital computer study was performed to help determine whether safety grounds should be placed at the work site or at adjacent towers. Literature reviews and approximate formulas were used in addition to detailed computer simulation. During an accidental line energization, single-phase, single-point grounding reduces phase-to-tower voltages, and on that basis is the prefered method, but measures must be taken to counteract the ground level step and touch potentials. After the study, a working three-phase transmission line model was constructed to help demonstrate the study results to linemen.
Keywords
Computer simulation; Contact resistance; Electric resistance; Electric shock; Grounding; Immune system; Poles and towers; Power transmission lines; Safety; Voltage;
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/TPAS.1984.318723
Filename
4112541
Link To Document