    Comparison of Generator Circuit-Breaker Stresses in Test Laboratory and Real Service Condition

  • Author

    Canay, I. M.

  • Author_Institution
    Canay Consultant
  • Volume
    21
  • Issue
    4
  • fYear
    2001
  • fDate
    4/1/2001 12:00:00 AM
  • Firstpage
    72
  • Lastpage
    72
  • Abstract
    The paper on hand shows that there may be substantial discrepancies regarding delayed current zeros and circuit-breaker arc energies when exposing a generator circuit-breaker to a short circuit in a real system or in a test lab. Depending on the preloading of the generator in the real system the degree of asymmetry may be far higher than that being adjustable in a test lab. Based on realistic generator data the courses of the short-circuit currents have been simulated for various cases also taking into account the arc voltages of different circuit-breaker types. For the same breaking current zero crossings may be delayed for several periods and arc energies may be substantially different in the real system compared to the test lab. Improved generator modeling is indispensable for correct simulation of such phenomena and explains "voltage depression."
  • Keywords
    Circuit breakers; Circuit faults; Circuit simulation; Circuit testing; Delay; Finite element methods; Laboratories; Stress; Surges; System testing; Generator circuit-breaker testing; circuit breaker arc energy; delayed current zero; short-circuit currents of generators; voltage depression;