DocumentCode
1175787
Title
Conservation voltage reduction (CVR) at Snohomish County PUD
Author
Kennedy, Barry W. ; Fletcher, R.H.
Author_Institution
Bonneville Power Admin., Portland, OR, USA
Volume
6
Issue
3
fYear
1991
fDate
8/1/1991 12:00:00 AM
Firstpage
986
Lastpage
998
Abstract
Results of field tests conducted on the Snohomish PUD´s distribution system to measure changes in energy consumption resulting from service voltage reduction are presented. The economic evaluation of the effects of voltage reduction is also examined. In addition, recommendations on continued research and development in conservation voltage reduction (CVR) application are discussed. Field tests to date have indicated a definite energy savings associated with voltage reduction and that these savings are extremely economical to capture. A combination of line drop compensation along with capacitor application is seen as a practical method to achieve CVR. Snohomish PUD has implemented a full scale CVR program in which the generated savings are transferred to neighboring utilities as a part of a conservation transfer agreement
Keywords
distribution networks; CVR; Snohomish County PUD; conservation voltage reduction; distribution networks; economic evaluation; energy savings; Energy capture; Energy consumption; Energy measurement; Environmental economics; Meeting planning; Power generation economics; Power system economics; Research and development; System testing; Voltage;
fLanguage
English
Journal_Title
Power Systems, IEEE Transactions on
Publisher
ieee
ISSN
0885-8950
Type
jour
DOI
10.1109/59.119238
Filename
119238
Link To Document