    Development and Installation of 275KV SF6 Gas-Insulated Transmission Line

  • Author

    Memita, N. ; Suzuki, T. ; Itaka, K. ; Furukawa, H. ; Kikuchi, K. ; Ninomiya, K.

  • Author_Institution
    The Kansai Electric Power Co., Inc.
  • Issue
    4
  • fYear
    1984
  • fDate
    4/1/1984 12:00:00 AM
  • Firstpage
    691
  • Lastpage
    698
  • Abstract
    In order to install a commercial 275kV gas-insulated transmission line (called GIL by the authors) on a route with many bends and inclines, a temperature rise test and long-term field test were performed to confirm the current capacity and thermo- mechanical and dielectric characteristics. Fault location and leakage gas removal tests were carried out to evaluate maintenance methods. Based on satisfactory results in all these tests, two circuits of 275kV GILs were installed to connect a gas-insulated substation of the Kansai Electric Power Co., Inc. to an overhead line.
  • Keywords
    Circuit testing; Conducting materials; Dielectrics; Gas insulated transmission lines; Substations; Sulfur hexafluoride; Surges; Switching circuits; Thermomechanical processes; Voltage;