• DocumentCode
    1175997
  • Title

    A novel method for incorporating weather effects in composite system adequacy evaluation

  • Author

    Billinton, R. ; Wenyuan, Li

  • Author_Institution
    Dept. of Electr. Eng., Saskatschewan Univ., Saskatoon, Sask., Canada
  • Volume
    6
  • Issue
    3
  • fYear
    1991
  • fDate
    8/1/1991 12:00:00 AM
  • Firstpage
    1154
  • Lastpage
    1160
  • Abstract
    The proposed method can recognize regional weather aspects including those situations in which transmission lines traverse several geographical regions which undergo different weather conditions. The method uses a Monte Carlo approach which can be readily applied to large-scale transmission systems. Case studies conducted using a program developed at the University of Saskatchewan show that neglecting all consideration of weather effects can lead to an optimistic assessment of system adequacy while ignoring regional weather conditions can result in overestimation of the resulting failure bunching effects due to adverse weather. The effects of weather variations on annualized indices are discussed, and the need to establish suitable and practical procedures for collecting adverse weather data which can be utilized in realistic composite system adequacy assessment is addressed. The modeling procedure also provides a realistic framework for practical data collection
  • Keywords
    Monte Carlo methods; power systems; Monte Carlo approach; adverse weather; composite system adequacy evaluation; failure bunching effects; regional weather aspects; transmission lines; weather effects; Failure analysis; Interconnected systems; Large-scale systems; Load flow analysis; Markov processes; Monte Carlo methods; Power engineering and energy; Power system analysis computing; Power systems; Power transmission lines;
  • fLanguage
    English
  • Journal_Title
    Power Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8950
  • Type

    jour

  • DOI
    10.1109/59.119260
  • Filename