• DocumentCode
    1176547
  • Title

    Study of Fast Synchronous-Reclosing Method for Parallel AC Line Fault in AC/DC Poer Transmission System

  • Author

    Doi, H. ; Mizukami, Y. ; Katsuki, K. ; Shimomura, T. ; Lyoda, L.

  • Author_Institution
    Kansai Electric Power Co., Inc.
  • Issue
    6
  • fYear
    1984
  • fDate
    6/1/1984 12:00:00 AM
  • Firstpage
    1135
  • Lastpage
    1141
  • Abstract
    In the AC/DC parallel system, AC power system is separated into two areas by the parallel AC line trip. As a result, it is necessary to recover from asynchronous operation. A method to close tripped AC line, "Fast synchronous-reclosing method", is proposed here. This paper consists of two parts: (1) Calculation of the frequency difference limit between the two areas. Energy function is formulated on the condition that fast synchronous-reclosing can be completed satisfactorily. (2) Confirmation of the performance of the fast synchronous-reclosing method in the AC/DC parallel line and frequency control before synchronous-reclosing and damping control of the power swing after reclosing, which were studied using an AC/DC simulator.
  • Keywords
    AC generators; Circuits; Frequency control; Power generation; Power system control; Power system simulation; Power system stability; Power systems; Power transmission lines; Transmission line theory;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1984.318440
  • Filename
    4112647