• DocumentCode
    1176732
  • Title

    Influence of Switching Conditions on the VETO Magnitudes in a GIS

  • Author

    Kumar, V. V. ; Thomas, J. M. ; Naidu, M. S.

  • Author_Institution
    Indian Institute of Science, Bangalore, India
  • Volume
    21
  • Issue
    6
  • fYear
    2001
  • fDate
    6/1/2001 12:00:00 AM
  • Firstpage
    72
  • Lastpage
    72
  • Abstract
    Estimation of very fast transient overvoltage (VFTO) has been carried out using EMTP for various switching conditions in a 420 kV gas-insulated substation (GIS). The variation of the VFTO peak along the GIS bus nodes for disconnector and circuit breaker switching operations, as well as the variation of VFTO peak with different magnitudes of trapped charges, have been studied. The results indicate a distinct pattern of variation of VFTO peak along the nodes of the GIS bus in the case of disconnector switch operation as compared to that of circuit-breaker operation. It has also been noticed that the variation of VFTO peak levels are not in direct proportion to the trapped charge present on the HV bus.
  • Keywords
    EMTP; Frequency domain analysis; Furnaces; Gas insulation; Geographic Information Systems; Substations; Switches; Switchgear; Switching circuits; Voltage control; EMTP; Gas insulated substation; disconnector switch; trapped charge; very fast transient overvoltages;
  • fLanguage
    English
  • Journal_Title
    Power Engineering Review, IEEE
  • Publisher
    ieee
  • ISSN
    0272-1724
  • Type

    jour

  • DOI
    10.1109/MPER.2001.4311440
  • Filename
    4311440