• DocumentCode
    1177534
  • Title

    Performance of a Fault-Current Limiter with a New Type of Direct-Cooled Tubular Element

  • Author

    Inaba, Tsuginori

  • Author_Institution
    High Voltage Power Laboratory Central Research Institute of Electric Power Industry (CRIEPI)
  • Issue
    7
  • fYear
    1984
  • fDate
    7/1/1984 12:00:00 AM
  • Firstpage
    1888
  • Lastpage
    1894
  • Abstract
    As one component of a fault-current limiter a high-speed acting type of high capacity current limiting fuse has been developed by using a direct forced cooling of the fusible tubular element. Although several coolants such as air, water, liquid nitrogen etc. were tested, water was recommended to be the best coolant. This kind of current limiter is available as not only an AC interrupter, but also a high-voltage DC interrupter for protection of thyristors in AC/DC substations and so on. The fault- current limiter consisting of multi-stage fuses could interrupt a prospective current of 7kA under a voltage of DC 40kV in l9ms after a fault occurrence.
  • Keywords
    Coolants; Cooling; Current limiters; Fuses; Interrupters; Nitrogen; Substation protection; Testing; Thyristors; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1984.318654
  • Filename
    4112759