• DocumentCode
    1178091
  • Title

    Operation of a Long-Term Transient Monitoring System in a 138-KV and a 500-KV Substation

  • Author

    Perkins, M.D. ; Mauser, S.F. ; Mikell, D.C. ; Nilsson, S.L.

  • Author_Institution
    Westinghouse Electric Corp.
  • Issue
    8
  • fYear
    1984
  • Firstpage
    2283
  • Lastpage
    2289
  • Abstract
    This paper describes the operating performance of automatic transient monitoring laboratories designed to capture fault and transient data on power systems. Laboratories were installed in a 138-kV and a 500-kV substation and operated for more than 25,000 hours over a three-year period. Recorded during this period were 341 events consisting of lightning, switching, and faul t transients. These results provide invaluable data on actual transients in power systems to aid power system equipment designers. A summary of the transient data obtained with the laboratories is contained in a companion paper. This work was sponsored by Electric Power Research Institute under Contract RP751-1.
  • Keywords
    Arresters; Laboratories; Monitoring; Power system faults; Power system modeling; Power system relaying; Power system transients; Senior members; Substations; Switches;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1984.318544
  • Filename
    4112818