• DocumentCode
    1178169
  • Title

    Influence of Hydro Units´ Generator-to-Turbine Inertia Ratio on Damping of Subsynchronous Oscillations

  • Author

    Andersson, G. ; Atmuri, R. ; Rosenqvist, R. ; Torseng, S.

  • Author_Institution
    ASEA
  • Issue
    8
  • fYear
    1984
  • Firstpage
    2352
  • Lastpage
    2361
  • Abstract
    The torsional data of hydro generators are examined and it is found that the inertia ratio between the generator and the turbine lies in the range of 10 to 40 and that the torsional frequency lies between 10 Hz and 24 Hz. It is shown that the high inherent generator to turbine inertia ratio of a hydro unit increases the modal damping at the torsional frequency significantly. This is substantiated by digital simulations for a generator connected to a series compensated AC network and by simulations on an HVDC-simulator for a generator feeding an HVDC-link. It is shown that with reasonable values of the turbine damping no torsional interactions problem would occur for the cases studied.
  • Keywords
    AC generators; Damping; Digital simulation; HVDC transmission; Hydraulic turbines; Rectifiers; Resonance; Resonant frequency; Shafts; Turbogenerators;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1984.318552
  • Filename
    4112826