DocumentCode
1178320
Title
Method for Estimation of the Remaining Lifetime of 6.6 KV XLPE Cables After Their First Failure in Service
Author
Gotoh, Hirofumi ; Okamoto, Tatsuki ; Suzuki, Sadao ; Tanaka, Toshikatsu
Author_Institution
Kyushu Electric Power Company
Issue
9
fYear
1984
Firstpage
2428
Lastpage
2434
Abstract
This paper describes a new method for estimation of the remaining useful life of a power cable which has failed and has then been repaired. The estimation is based on our observation of the lengths of vented and bow-tie water trees in a section of cable that was removed during repair, calculation of the rate at which these trees grew during the period of service, the level of AC or impulse breakdown strength at which failure will occur again, and the assumption that water trees grow in the same manner before failure and after repair. A new concept of "maximum tree length" is introduced as a numerical parameter which can be used to characterize the relation between the length and number of trees in calculating the growth rate. The maximum tree length l depends on both the length and conditions of service before failure occurred.
Keywords
Aging; Cable insulation; Conductors; Electric breakdown; Life estimation; Lifetime estimation; Power cables; Stress control; Trees - insulation; Underwater cables;
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/TPAS.1984.318395
Filename
4112844
Link To Document