• DocumentCode
    1178551
  • Title

    Short-Circuit Current Partitioning in HV Substations in Ring-Bus Arrangement with Redundancy

  • Author

    Koeppi, G. ; Blahous, L. ; Hager, H.

  • Author_Institution
    BBC Brown, Boveri & Company, Ltd.
  • Issue
    9
  • fYear
    1984
  • Firstpage
    2651
  • Lastpage
    2658
  • Abstract
    This paper proposes a way of reducing the short-circuit current stress imposed on individual circuit-breakers. A ring bus arrangement permits partitioning of the current, which is distributed between two circuit-breakers by splitting up the ring during fault clearing. This means that, in the ideal case, the circuit-breakers could be used up to fault levels of twice their rated interrupting capability. The "splitting" function is so easy to perform that any breaker can be expected to accomplish it with high reliability.
  • Keywords
    Availability; Circuit faults; Circuit testing; Costs; Current limiters; Medium voltage; Protection; Redundancy; Stress; Substations;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1984.318237
  • Filename
    4112870