Preventing Failures in Outdoor Distribution-Class Metalclad Switchgear
Author :
VanHaeren, R. ; Stone, G.C. ; Meehan, J. ; Kurtz, M.
Author_Institution :
Ontario Hydro
Issue :
10
fYear :
1985
Firstpage :
2706
Lastpage :
2712
Abstract :
Failure of the insulation in distribution- class metalclad switchgear may release large amounts of energy resulting in an explosive hazard to adjacent equipment and personnel. Many such failures have occurred in older outdoor and generating station switchgear within Ontario Hydro. The failures have often been caused by partial discharge (PD) activity and surface tracking which destroy organic bus support insulation. Test methods have evolved to help locate deteriorating insulation in the field, and to qualify new insulation systems. The life of the switchgear can often be extended by incorporating appropriate preventive maintenance.
Keywords :
Explosives; Hazards; Insulation life; Insulation testing; Partial discharges; Personnel; Preventive maintenance; Surface discharges; Switchgear; System testing;