• DocumentCode
    1179354
  • Title

    Application of Special Arresters on 138 kV Lines of Application Power Company

  • Author

    Shih, C.H. ; Hayes, R.M. ; Nichols, D.K. ; Koch, R.E. ; Timoshenko, J.A. ; Anderson, J.G.

  • Author_Institution
    American Electric Power Service Corporation
  • Issue
    10
  • fYear
    1985
  • Firstpage
    2857
  • Lastpage
    2863
  • Abstract
    Special zinc oxide series gapped line arresters were installed on Appalachian Power Company 138 kV lines having high tower footing resistance and severe lightning exposure. This effort was part of an experiment to explore means of reducing lightning flashovers in exposed locations where low ground resistances are not feasible. Because of possible future voltage uprating of these lines, the arresters were built in the form of high strength nonporcelain mechanical struts, designed to limit phase conductor swing. This paper describes the field installation of these experimental arresters and their instrumentation and reports operating experience in 1983.
  • Keywords
    Arresters; Circuit testing; Conductors; Electric resistance; Electron tubes; Flashover; Insulation; Lightning; Poles and towers; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1985.319130
  • Filename
    4112954