DocumentCode :
1179806
Title :
Voltage Recovery after Unbalanced and Balanced Voltage Dip in Three-Phase Systems
Author :
Bollen, Math H. J.
Author_Institution :
Chalmers University of Technology, Gothenburg, Sweden
Volume :
22
Issue :
10
fYear :
2002
Firstpage :
63
Lastpage :
64
Abstract :
This paper studies the recovery of the voltage after a voltage dip due to a fault in a three-phase system. The instant of voltage recovery corresponds to the instant of fault clearing. For single-phase and phase-to-phase faults a single point-on-wave of voltage recovery can be defined. For two-phase-to-ground and three-phase faults the recovery takes place in two or three steps. The voltage recovery is described in a systematic way by using a classification of three-phase unbalanced voltage dips. The voltage recovery needs to be modeled correctly for studies of equipment immunity against voltage dips.
Keywords :
Capacitors; Gaussian distribution; Guidelines; Harmonic analysis; Nonlinear equations; Power system harmonics; Power system modeling; Resonance; Temperature distribution; Voltage fluctuations; Power quality; equipment immunity; power transmission and distribution; voltage dips (sags);