• DocumentCode
    1179922
  • Title

    A Tapping Range and Voltage Level Analysis Chart for Tap Changing Transformers

  • Author

    Baitch, A. ; Barr, R.A.

  • Author_Institution
    Hazemeyer-Holec (Aust.) Pty. Ltd.
  • Issue
    11
  • fYear
    1985
  • Firstpage
    3269
  • Lastpage
    3277
  • Abstract
    The operation of On Line Tap Changing (O.L.T.C.) transformers is subject to many power system variables and characteristics. These conditions include voltage variations, load fluctuations, transformer configurations and settings of tap changing relays. In this paper a graphical method is presented which simplifies analysis of O.L.T.C. transformer operation for variation in all the power system parameters. The graphical method eliminates the need for tedious repetitive calculations and allows the distribution engineer to readily determine transformer tapping requirements. The tapping range compatability of existing transformers can easily be determined in addition to the optimisation of system voltage float levels.
  • Keywords
    Australia; Control systems; Power engineering and energy; Power generation; Power system analysis computing; Power system relaying; Substations; Transformers; Voltage control; Voltage fluctuations;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1985.318841
  • Filename