• DocumentCode
    1181211
  • Title

    A Practical Fault Location Approach for Double Circuit Transmission Lines Using Single End Data

  • Author

    Kawady, T. A. ; Stenzel, Jonas

  • Author_Institution
    Darmstadt University of Technology
  • Volume
    22
  • Issue
    12
  • fYear
    2002
  • Firstpage
    62
  • Lastpage
    63
  • Abstract
    Double circuit transmission lines are frequently subjected to a variety of technical problems from the perspective of protection engineering. These problems are mainly due to the mutual coupling effects between adjacent circuits of the line. A new fault location approach for double circuit transmission lines is introduced. It depends only on the data extracted from one end of the line. This practically facilitates implementing and developing this approach, as it needs no information from the other end. The approach is based on modifying the apparent impedance method using modal transformation. Depending on modal transformation the coupled equations of the transmission line are converted into decoupled ones. This greatly eliminates the mutual effects resulting in an accurate estimation for the fault distance in a straightforward manner. Also, the effects of prefault currents, charging currents, and the unknown fault resistance on the estimation accuracy are compensated. The proposed approach was tested via digital simulation using ATP-EMTP in conjunction with MATLAB. Applied test results corroborate the superior performance of the proposed approach.
  • Keywords
    Circuit faults; Data mining; Distributed parameter circuits; Equations; Fault location; Impedance measurement; Mutual coupling; Protection; Testing; Transmission lines; ATP; digital protection; fault location; modal transformation; mutual coupling; parallel transmission lines;
  • fLanguage
    English
  • Journal_Title
    Power Engineering Review, IEEE
  • Publisher
    ieee
  • ISSN
    0272-1724
  • Type

    jour

  • DOI
    10.1109/MPER.2002.4311921
  • Filename
    4311921