DocumentCode
1181263
Title
Voltages Induced by Lightning Strokes and Ground-Faults on a Coaxial Telecom Circuit Enclosed in a Composite Earthwire Part I: General Approach and Earth Faults Induced Voltages
Author
Kouteynikoff, P. ; Anzanel, P.
Author_Institution
ELECTRICITE de FRANCE-DER/ERMEL
Issue
4
fYear
1985
fDate
7/1/1985 12:00:00 AM
Firstpage
839
Lastpage
845
Abstract
This paper presents the first part of a comprehensive research program about the problem of maximum induced voltages inside a composite coaxial earthwire for overhead transmission lines (the coaxial pair being used as a private telecommunication circuit). Based on the concept of transfer impedance, one can derive a general four steps calculation procedure valid for both cases of lightning strokes and earth faults. The problem of voltage induced by phase to earth faults is dealt with in Part I where unpublished experimental results on saturation effects in composite earthwire at 50 Hz and a parametric analysis of induced voltages are presented. Practical values of maximum induced voltages are given.
Keywords
Circuit faults; Coaxial cables; Coaxial components; Earth; Lightning; Power cable insulation; Power cables; Power transmission lines; Telecommunications; Voltage;
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/TPAS.1985.319084
Filename
4113164
Link To Document