• DocumentCode
    1181263
  • Title

    Voltages Induced by Lightning Strokes and Ground-Faults on a Coaxial Telecom Circuit Enclosed in a Composite Earthwire Part I: General Approach and Earth Faults Induced Voltages

  • Author

    Kouteynikoff, P. ; Anzanel, P.

  • Author_Institution
    ELECTRICITE de FRANCE-DER/ERMEL
  • Issue
    4
  • fYear
    1985
  • fDate
    7/1/1985 12:00:00 AM
  • Firstpage
    839
  • Lastpage
    845
  • Abstract
    This paper presents the first part of a comprehensive research program about the problem of maximum induced voltages inside a composite coaxial earthwire for overhead transmission lines (the coaxial pair being used as a private telecommunication circuit). Based on the concept of transfer impedance, one can derive a general four steps calculation procedure valid for both cases of lightning strokes and earth faults. The problem of voltage induced by phase to earth faults is dealt with in Part I where unpublished experimental results on saturation effects in composite earthwire at 50 Hz and a parametric analysis of induced voltages are presented. Practical values of maximum induced voltages are given.
  • Keywords
    Circuit faults; Coaxial cables; Coaxial components; Earth; Lightning; Power cable insulation; Power cables; Power transmission lines; Telecommunications; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1985.319084
  • Filename
    4113164