Electrical resistance data from fault tests for 2/0 and 4/0 temporary grounding jumpers
Author :
Kolcio, Nestor ; Brown, Kenneth J. ; Page, W. John
Author_Institution :
American Electr. Power, Gahanna, OH, USA
Volume :
18
Issue :
2
fYear :
2003
fDate :
4/1/2003 12:00:00 AM
Firstpage :
436
Lastpage :
441
Abstract :
The paper provides ranges of resistance values for 2/0 and 4/0 temporary grounding jumpers (TG jumpers) which when subjected to rated fault tests sustained: (a) no damage, (b) some fusing, and (c) failed by separation. This information is unique and can be used for establishing minimum resistance values for TG jumper testing and selecting pass/fail criterion. The results were obtained from special tests conducted at Bonneville Power Administration and Ontario Hydro Power Technologies high current laboratories.
Keywords :
cables (electric); earthing; electric resistance measurement; power system faults; testing; 2/0 temporary grounding jumpers; 4/0 temporary grounding jumpers; Bonneville Power Administration; Ontario Hydro Power Technologies; cable ends; clamps; electrical resistance data; fault tests; ferrules; fusing; high current laboratories; minimum resistance values; pass/fail criterion selection; rated fault tests; separation; testing; Cables; Clamps; Copper; Electric resistance; Electrical resistance measurement; Grounding; Inspection; Laboratories; Life testing; Performance evaluation;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/TPWRD.2003.809608
Filename :
1193861
Link To Document :
بازگشت