Lightning flashovers on 77-kV systems: observed voltage bias effects and analysis
Author
Ito, Takamitsu ; Ueda, Toshiaki ; Watanabe, Hideto ; Funabashi, Toshihisa ; Ametani, Akihiro
Author_Institution
Meidensha Corp., Tokyo, Japan
Volume
18
Issue
2
fYear
2003
fDate
4/1/2003 12:00:00 AM
Firstpage
545
Lastpage
550
Abstract
Twenty-nine backflashovers were recorded on a 77-kV double-circuit transmission line with single overhead groundwire. Twenty-six of these occurred on phases where power-frequency voltage bias was positive. EMTP analysis of the line shows that the multistory tower model, recommended by the Japanese Guideline of Insulation Design/Coordination against Lightning, suggests a stronger influence of phase position than was observed. Best simulation results were obtained with a simple tower model of constant surge impedance.
Keywords
EMTP; digital simulation; flashover; poles and towers; power overhead lines; surges; 77 kV; EMTP analysis; Japanese Guideline of Insulation Design/Coordination; backflashovers; constant surge impedance; double-circuit transmission line; lightning flashovers; multistory tower model; phase position; positive power-frequency voltage bias; single overhead groundwire; summer lightning; transient analysis; voltage bias effects; EMTP; Flashover; Guidelines; Insulation; Lightning; Poles and towers; Power overhead lines; Power system modeling; Power transmission lines; Voltage;