Abstract :
The results of a field test conducted for a static VAr compensator installed at a 500 kV substation are presented. The static VAr compensator improved power system damping performance significantly by increasing the synchronizing and damping torques. Frequency-response analysis was used for examining the synchronizing and damping torques. The test cases were simulated using time-domain analysis, and results agreed well with the results of the field testing
Keywords :
damping; static VAr compensators; substations; testing; 500 kV; damping torques; field testing; frequency response analysis; power system damping; static VAr compensators; substations; synchronising torques; time-domain analysis; Control systems; Damping; Frequency synchronization; Power system simulation; Power systems; Static VAr compensators; Substations; System testing; Thyristors; Voltage control;