DocumentCode
1181736
Title
A field test of power swing damping by static VAr compensator
Author
Sawa, T. ; Shirai, Y. ; Michigami, T. ; Sakanaka, Y. ; Uemura, Y.
Author_Institution
Tokyo Electr. Power Co., Japan
Volume
4
Issue
3
fYear
1989
fDate
8/1/1989 12:00:00 AM
Firstpage
1115
Lastpage
1121
Abstract
The results of a field test conducted for a static VAr compensator installed at a 500 kV substation are presented. The static VAr compensator improved power system damping performance significantly by increasing the synchronizing and damping torques. Frequency-response analysis was used for examining the synchronizing and damping torques. The test cases were simulated using time-domain analysis, and results agreed well with the results of the field testing
Keywords
damping; static VAr compensators; substations; testing; 500 kV; damping torques; field testing; frequency response analysis; power system damping; static VAr compensators; substations; synchronising torques; time-domain analysis; Control systems; Damping; Frequency synchronization; Power system simulation; Power systems; Static VAr compensators; Substations; System testing; Thyristors; Voltage control;
fLanguage
English
Journal_Title
Power Systems, IEEE Transactions on
Publisher
ieee
ISSN
0885-8950
Type
jour
DOI
10.1109/59.32607
Filename
32607