GIC Occurrences and CIC Tests for 400 KV System Transformer
Author :
Lahtinen, M. ; Elovaara, J.
Volume :
22
Issue :
3
fYear :
2002
fDate :
3/1/2002 12:00:00 AM
Firstpage :
63
Lastpage :
63
Abstract :
The geomagnetic induced currents in a transmission network may saturate transformers and cause additional losses, a high level of harmonics, and a lack of reactive power in the grid. Malfunctioning of protection circuits is also reported in the literature. The field tests made for two 463 MVA system transformers show that tested transformers may tolerate very high dc currents for times typical to geomagnetic storms. The effects for the voltage control and voltage quality in network are also considered and results of earlier Finnish GIC risk studies are reported.
Keywords :
Circuit faults; Circuit testing; Geomagnetism; Power system harmonics; Power system protection; Propagation losses; Reactive power; Storms; System testing; Voltage control; Transformer; dc-current; geomagnetic; immunity;