DocumentCode :
1183282
Title :
Experimental Results of a Supplementary Technique for Auto-Reclosing EHV/UHV Transmission Lines
Author :
Eissa, M. M. ; Malik, O. P.
Author_Institution :
Helwan University, Cairo, Egypt; University of Calgary, Alberta, Canada
Volume :
22
Issue :
4
fYear :
2002
fDate :
4/1/2002 12:00:00 AM
Firstpage :
78
Lastpage :
78
Abstract :
A technique to discriminate between the line charging inrush current and the current resulting on closing or auto-reclosing a faulted EHV/UHV transmission line has been implemented on a 32-bit digital signal processor (DSP) board. The technique is based on the voltage signals before switching and the current signals. This technique is proposed to be a supplement to the main protection schemes for both single-circuit and double-circuit lines. The scheme is tested on a physical model of a transmission system with a source at each end. Laboratory tests show that the proposed technique is effective for three-pole and single-pole reclosing on a faulted or healthy line.
Keywords :
Concurrent computing; Digital signal processing; Digital signal processors; Laboratories; Power system transients; Power transmission lines; Surge protection; System testing; Transmission lines; Voltage; Computer relaying; auto-reclosing; parallel and single lines; real-time implementation;
fLanguage :
English
Journal_Title :
Power Engineering Review, IEEE
Publisher :
ieee
ISSN :
0272-1724
Type :
jour
DOI :
10.1109/MPER.2002.4312147
Filename :
4312147
Link To Document :
بازگشت