DocumentCode
1183509
Title
Protection technique based on Δ-zero sequence voltages for generator stator ground fault
Author
Tai, N.L. ; Ai, Q.
Author_Institution
Dept. of Power Electr. Eng., Shanghai Jiao Tong Univ., China
Volume
151
Issue
5
fYear
2004
Firstpage
651
Lastpage
657
Abstract
A mathematical model on a coil basis is used to study the characteristics of the zero sequence voltage of a generator. The proposed technique for the stator ground fault detection simultaneously takes into account the fault contributed zero sequence fundamental voltage and the fault contributed third-harmonic voltage (Δ-zero sequence voltage). The effect of the start-up component based on the wavelet transform is also highlighted. As information both on the fault contributed zero sequence fundamental voltage and the third-harmonic voltage is used simultaneously, the scheme can obtain higher sensitivity. Results from the experiment and in the field show that the proposed technique can detect the ground fault with high sensitivity and reliability during all operating conditions.
Keywords
coils; electric generators; fault diagnosis; harmonic distortion; harmonics suppression; machine protection; reliability; stators; wavelet transforms; Δ-zero sequence voltages; coils; fault contributed third-harmonic voltage; fundamental voltage; generator fault; mathematical model; protection technique; reliable operating conditions; sensitivity; start-up component; stator ground fault detection; wavelet transform;
fLanguage
English
Journal_Title
Generation, Transmission and Distribution, IEE Proceedings-
Publisher
iet
ISSN
1350-2360
Type
jour
DOI
10.1049/ip-gtd:20040644
Filename
1367431
Link To Document