• DocumentCode
    1183509
  • Title

    Protection technique based on Δ-zero sequence voltages for generator stator ground fault

  • Author

    Tai, N.L. ; Ai, Q.

  • Author_Institution
    Dept. of Power Electr. Eng., Shanghai Jiao Tong Univ., China
  • Volume
    151
  • Issue
    5
  • fYear
    2004
  • Firstpage
    651
  • Lastpage
    657
  • Abstract
    A mathematical model on a coil basis is used to study the characteristics of the zero sequence voltage of a generator. The proposed technique for the stator ground fault detection simultaneously takes into account the fault contributed zero sequence fundamental voltage and the fault contributed third-harmonic voltage (Δ-zero sequence voltage). The effect of the start-up component based on the wavelet transform is also highlighted. As information both on the fault contributed zero sequence fundamental voltage and the third-harmonic voltage is used simultaneously, the scheme can obtain higher sensitivity. Results from the experiment and in the field show that the proposed technique can detect the ground fault with high sensitivity and reliability during all operating conditions.
  • Keywords
    coils; electric generators; fault diagnosis; harmonic distortion; harmonics suppression; machine protection; reliability; stators; wavelet transforms; Δ-zero sequence voltages; coils; fault contributed third-harmonic voltage; fundamental voltage; generator fault; mathematical model; protection technique; reliable operating conditions; sensitivity; start-up component; stator ground fault detection; wavelet transform;
  • fLanguage
    English
  • Journal_Title
    Generation, Transmission and Distribution, IEE Proceedings-
  • Publisher
    iet
  • ISSN
    1350-2360
  • Type

    jour

  • DOI
    10.1049/ip-gtd:20040644
  • Filename
    1367431