DocumentCode
1183703
Title
A differential line protection scheme for power systems based on composite voltage and current measurements
Author
Aggarwal, R.K. ; Johns, A.T.
Author_Institution
Sch. of Electr. Eng., Bath Univ., UK
Volume
4
Issue
3
fYear
1989
fDate
7/1/1989 12:00:00 AM
Firstpage
1595
Lastpage
1601
Abstract
A differential feeder protection that utilizes voltage and current signals is described. This approach obviates the need for relay bias to compensate for capacitance spill current, thus improving the relay sensitivity. From a practical point of view, the scheme has been designed to simplify the digital hardware requirements and reduce the bandwidth requirements for signal transmission over a fiber-optic link
Keywords
electric current measurement; power system measurement; power system protection; relay protection; voltage measurement; capacitance spill current; current measurements; differential feeder protection; fiber-optic link; power system relay protection; signal transmission; voltage measurement; Capacitance; Circuit faults; Current measurement; Digital relays; Fault currents; Power system measurements; Power system protection; Power system relaying; Protective relaying; Voltage;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.32648