• DocumentCode
    1183703
  • Title

    A differential line protection scheme for power systems based on composite voltage and current measurements

  • Author

    Aggarwal, R.K. ; Johns, A.T.

  • Author_Institution
    Sch. of Electr. Eng., Bath Univ., UK
  • Volume
    4
  • Issue
    3
  • fYear
    1989
  • fDate
    7/1/1989 12:00:00 AM
  • Firstpage
    1595
  • Lastpage
    1601
  • Abstract
    A differential feeder protection that utilizes voltage and current signals is described. This approach obviates the need for relay bias to compensate for capacitance spill current, thus improving the relay sensitivity. From a practical point of view, the scheme has been designed to simplify the digital hardware requirements and reduce the bandwidth requirements for signal transmission over a fiber-optic link
  • Keywords
    electric current measurement; power system measurement; power system protection; relay protection; voltage measurement; capacitance spill current; current measurements; differential feeder protection; fiber-optic link; power system relay protection; signal transmission; voltage measurement; Capacitance; Circuit faults; Current measurement; Digital relays; Fault currents; Power system measurements; Power system protection; Power system relaying; Protective relaying; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.32648