    Power Line Carrier Experience on the Vancouver Island HVDC Tie

  • Author

    Treasure, T.R.

  • Author_Institution
    British Columbia Hydro and Power Authority
  • Issue
    1
  • fYear
    1979
  • Firstpage
    318
  • Lastpage
    322
  • Abstract
    Noise from an HVDC converter station prevented satisfactory operation of a power line carrier system coupled between ground and a low voltage dc neutral transmission line leaving the station. The author presents noise spectrum measurements of the noise which originates from the HVDC neutral bus. A "T" type of wave trap is described which prevents the noise on the HVDC neutral bus from being transmitted to the low voltage dc neutral transmission line.
  • Keywords
    Coaxial cables; Frequency; HVDC transmission; Noise figure; Noise measurement; Noise reduction; Programmable control; Signal to noise ratio; Transmitters; Underwater cables;