DocumentCode :
1183788
Title :
Power Line Carrier Experience on the Vancouver Island HVDC Tie
Author :
Treasure, T.R.
Author_Institution :
British Columbia Hydro and Power Authority
Issue :
1
fYear :
1979
Firstpage :
318
Lastpage :
322
Abstract :
Noise from an HVDC converter station prevented satisfactory operation of a power line carrier system coupled between ground and a low voltage dc neutral transmission line leaving the station. The author presents noise spectrum measurements of the noise which originates from the HVDC neutral bus. A "T" type of wave trap is described which prevents the noise on the HVDC neutral bus from being transmitted to the low voltage dc neutral transmission line.
Keywords :
Coaxial cables; Frequency; HVDC transmission; Noise figure; Noise measurement; Noise reduction; Programmable control; Signal to noise ratio; Transmitters; Underwater cables;