DocumentCode :
1183946
Title :
A New Digital Feed Circuit Protection Using Directional Element
Author :
Eissa, M.M.
Author_Institution :
King Abdul-Aziz Univ., Jeddah
Volume :
24
Issue :
2
fYear :
2009
fDate :
4/1/2009 12:00:00 AM
Firstpage :
531
Lastpage :
537
Abstract :
The paper presents the application of a new directional relaying principle to a tapped feeder. The possibility of failure to trip for a fault on the protected line must be taken into account when supply to at least one of the line terminals is cut off or when the keying element sensitivity is insufficient. This has been achieved by using the pre-fault voltage and fault current signals. The pre-fault voltage signal is compensated to be synchronized with the fault current signal. Two directional quantities are derived at the buses that have two circuits. A fault characteristic is suggested to easily identify the forward and reverse faults.
Keywords :
digital circuits; multiterminal networks; relays; digital feed circuit protection; directional element; fault characteristics; multiterminal line; tapped circuits; tapped feeder; Directionality; fault characteristics; multiterminal line; tapped circuits;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/TPWRD.2009.2013374
Filename :
4797801
Link To Document :