DocumentCode :
1183980
Title :
Sensitivity of Transformer´s Hottest Spot and Equivalent Aging to Selected Parameters
Author :
Peterchuck, D. ; Pahwa, Anil
Author_Institution :
Omaha Public Power District; Kansas State University
Volume :
22
Issue :
5
fYear :
2002
fDate :
5/1/2002 12:00:00 AM
Firstpage :
70
Lastpage :
70
Abstract :
In 1995, IEEE released a revised Transformer Loading Guide, which includes an Annex G that contains an additional set of transformer temperature equations that incorporate oil flow phenomena, changing ambient air temperature, and account for the change in resistivity of the winding due to heating. These new equations involve empirical exponent variables that account for properties of the transformer. This paper investigates sensitivity of hottest spot temperature and equivalent aging of transformer with respect to these variables. By varying these variables under various load conditions and by Monte Carlo simulation with different probability distributions of these variables, their importance in the transformer model and their influence in modeling accuracy pertaining to the Annex G equations have been obtained.
Keywords :
Aging; Equations; Magnetic flux; Oil insulation; Petroleum; Power transformer insulation; Power transformers; Surges; Temperature sensors; Testing; Monte Carlo methods; Power transformer; insulation aging; transformer windings;
fLanguage :
English
Journal_Title :
Power Engineering Review, IEEE
Publisher :
ieee
ISSN :
0272-1724
Type :
jour
DOI :
10.1109/MPER.2002.4312223
Filename :
4312223
Link To Document :
بازگشت