• DocumentCode
    1184025
  • Title

    A Hybrid Islanding Detection Technique Using Average Rate of Voltage Change and Real Power Shift

  • Author

    Mahat, Pukar ; Chen, Zhe ; Bak-Jensen, Birgitte

  • Author_Institution
    Inst. of Energy Technol., Aalborg Univ., Aalborg
  • Volume
    24
  • Issue
    2
  • fYear
    2009
  • fDate
    4/1/2009 12:00:00 AM
  • Firstpage
    764
  • Lastpage
    771
  • Abstract
    The mainly used islanding detection techniques may be classified as active and passive techniques. Passive techniques don´t perturb the system but they have larger non-detection zones, whereas active techniques have smaller non-detection zones but they perturb the system. In this paper, a new hybrid technique is proposed to solve this problem. An average rate of voltage change (passive technique) has been used to initiate a real power shift (active technique), which changes the real power of distributed generation (DG), when the passive technique cannot have a clear discrimination between islanding and other events in the system. Simulation results show that the proposed method is effective in detecting islanding of distribution systems with DGs.
  • Keywords
    distributed power generation; active technique; distributed generation; hybrid islanding detection technique; passive techniques; real power shift; Distributed generation; islanding detection; real power shift; voltage change;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.2009.2013376
  • Filename
    4797808