DocumentCode
1184583
Title
Comparison of performance of switching technologies on E Cigre motor simulation circuit
Author
Gibbs, J.D. ; Koch, D. ; Malkin, P. ; Cornick, K.J.
Author_Institution
Merlin Gerin, Grenoble, France
Volume
4
Issue
3
fYear
1989
fDate
7/1/1989 12:00:00 AM
Firstpage
1745
Lastpage
1750
Abstract
The Cigre motor simulation circuit is used to perform comparative switching tests with modern technologies, i.e. SF6 and vacuum. The tests are aimed at comparing the overvoltage performance of medium-voltage circuit breakers in an accepted, standard circuit. The results are assessed in terms of the likely effects on main and interturn machine insulation. All types of switching devices tested generated acceptable levels of overvoltages due to simple current chopping in the circuit used. That is, the overvoltages generated were below the level at which motor insulation should be at risk. The phenomenon of multiple restriking was relatively frequently observed
Keywords
circuit breakers; electric motors; testing; E Cigre motor simulation circuit; MV circuit breakers; SF6 circuit breakers; current chopping; interturn machine insulation; multiple restriking; overvoltage performance; testing; vacuum circuit breakers; Circuit breakers; Circuit simulation; Circuit testing; Inductance; Production; Shape; Sulfur hexafluoride; Switching circuits; Vacuum arcs; Voltage control;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.32668
Filename
32668
Link To Document