DocumentCode :
1184592
Title :
Arcing phenomena and their application for fault location in SF6-insulated equipment
Author :
Ushida, K. ; Takagi, I. ; Maruyama, S. ; Sakakibara, T. ; Kamata, I.
Author_Institution :
Chubu Electr. Power Co., Nagoya, Japan
Volume :
4
Issue :
3
fYear :
1989
fDate :
7/1/1989 12:00:00 AM
Firstpage :
1751
Lastpage :
1756
Abstract :
A system is presented for locating faults by measuring time lags in the propagation of gas pressure shock waves caused by ground faults in GIS (gas-insulated substation) and GIB (gas-insulated bus) equipment. For sensors, the system uses shock gas pressure relays of an optical signal transmission type. It is well designed, with few sensors, to locate faults with high accuracy. Also presented are results of an extensive arc test conducted on actual equipment when developing the system, and some applications of the system in substations are described
Keywords :
arcs (electric); electric sensing devices; fault location; gaseous insulation; substations; sulphur compounds; GIB; GIS; fault location; gas-insulated buses; gas-insulated substation; optical signal transmission shock gas pressure relays; Fault location; Gas detectors; Geographic Information Systems; Optical propagation; Optical sensors; Pressure measurement; Sensor phenomena and characterization; Shock waves; Substations; Time measurement;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.32669
Filename :
32669
Link To Document :
بازگشت