DocumentCode
1184664
Title
Five-legged core transformer equivalent circuit
Author
Stuehm, Don L. ; Mork, Bruce A. ; Mairs, Dan D.
Author_Institution
North Dakota State Univ., Fargo, ND, USA
Volume
4
Issue
3
fYear
1989
fDate
7/1/1989 12:00:00 AM
Firstpage
1786
Lastpage
1793
Abstract
Cable-fed five-legged core grounded-wye-to-grounded-wye transformers can cause excessively high voltages in a power system. A typical per-phase equivalent does not adequately represent a five-legged core transformer for the steady-state or transient analyses required in investigating overvoltages. A three-phase equivalent circuit is developed. Comparison of the result for the equivalent circuit and test results show good agreement
Keywords
equivalent circuits; overvoltage; power transformers; transformer testing; transients; 3-phase equivalent circuit; cable-fed 5-legged core transformer; grounded-wye-to-grounded-wye transformers; overvoltages; steady-state analyses; transient analyses; Circuit testing; Equivalent circuits; Ferroresonance; IEEE members; Leg; Phase transformers; Power cables; Power system modeling; Surges; Transformer cores;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.32674
Filename
32674
Link To Document