Abstract :
An 800 kV metal oxide transmission line surge arrester (TLA) has been developed, installed, and tested on the AEP 765 kV Marysville to Kammer transmission line. The purpose of this transmission line surge arrester (TLA) is to pave the way for the development, construction, and application of an 800 kV SF6 dead tank circuit breaker without closing resistors and free standing current transformers at AEP´s 800 kV Orange station. The maximum design operating voltage is 800 kV, and 765 kV is the nominal operating voltage. Successful field test results of the TLA´s ability to limit switching overvoltage emanating from circuit breaker operation to below the transmission line switching withstand are given. Successful test results of the 800 kV dead tank circuit breaker design dielectric test are given.
Keywords :
Arresters; Circuit breakers; Circuit testing; Current transformers; Distributed parameter circuits; Power system transients; Resistors; Sulfur hexafluoride; Surges; Switching circuits; Transmission line surge arrester (TLA); circuit breaker; closing resistor; oil filled current transformer; polymer; station class surge arrester (SA); switching overvoltage;
Journal_Title :
Power Engineering Review, IEEE
DOI :
10.1109/MPER.2002.4312307