• DocumentCode
    1185029
  • Title

    A simplified lumped parameter model for finding distribution transformer and secondary system responses to lightning

  • Author

    Smith, D.R. ; Puri, J.L.

  • Author_Institution
    Westinghouse Electr. Corp., Pittsburgh, PA, USA
  • Volume
    4
  • Issue
    3
  • fYear
    1989
  • fDate
    7/1/1989 12:00:00 AM
  • Firstpage
    1927
  • Lastpage
    1936
  • Abstract
    The results of other investigations on distribution transformer and system response to lightning strokes to the primary terminal of the transformer are briefly reviewed, from the standpoint of system and transformer currents, and service entrance phase-to-neutral voltage. A simplified lumped parameter model for the transformer and associated distribution system is described. The analysis of this model yields equations for the quantitative determination of the influence of system parameters on the lightning-induced surge currents in distribution transformers, and the service entrance phase-to-neutral voltages
  • Keywords
    lightning; power transformers; surges; distribution transformer; lightning response; lightning strokes; lightning-induced surge currents; lumped parameter model; service entrance phase-to-neutral voltage; transformer currents; Arresters; Automatic testing; Conductors; EMTP; Equations; Impedance; Inductance; Lightning; Surges; System testing;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.32692
  • Filename
    32692