DocumentCode
1185029
Title
A simplified lumped parameter model for finding distribution transformer and secondary system responses to lightning
Author
Smith, D.R. ; Puri, J.L.
Author_Institution
Westinghouse Electr. Corp., Pittsburgh, PA, USA
Volume
4
Issue
3
fYear
1989
fDate
7/1/1989 12:00:00 AM
Firstpage
1927
Lastpage
1936
Abstract
The results of other investigations on distribution transformer and system response to lightning strokes to the primary terminal of the transformer are briefly reviewed, from the standpoint of system and transformer currents, and service entrance phase-to-neutral voltage. A simplified lumped parameter model for the transformer and associated distribution system is described. The analysis of this model yields equations for the quantitative determination of the influence of system parameters on the lightning-induced surge currents in distribution transformers, and the service entrance phase-to-neutral voltages
Keywords
lightning; power transformers; surges; distribution transformer; lightning response; lightning strokes; lightning-induced surge currents; lumped parameter model; service entrance phase-to-neutral voltage; transformer currents; Arresters; Automatic testing; Conductors; EMTP; Equations; Impedance; Inductance; Lightning; Surges; System testing;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.32692
Filename
32692
Link To Document