DocumentCode :
1185087
Title :
Estimation of flashover rates of overhead power distribution lines by lightning strokes to nearby ground
Author :
Chowdhuri, P.
Author_Institution :
Center for Electr. Power, Tennessee Technol. Univ., Cookeville, TN, USA
Volume :
4
Issue :
3
fYear :
1989
fDate :
7/1/1989 12:00:00 AM
Firstpage :
1982
Lastpage :
1989
Abstract :
A method is proposed for calculating the flashover of an overhead power distribution line caused by lightning strokes to nearby ground. The results are presented in the form of a graph of flashover rate vs. BIL (basic impulse insulation level) for a 10 m high line and ground flash density of 10/km2/year. Flashover rates of lines of different heights and ground flash densities can be estimated from this graph
Keywords :
flashover; lightning; power overhead lines; basic impulse insulation level; flashover rates; ground flash densities; lightning strokes; overhead power distribution lines; Clouds; Electrostatics; Flashover; Lightning; Magnetic fields; Power distribution; Power distribution lines; Power system reliability; Statistical distributions; Voltage;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.32698
Filename :
32698
Link To Document :
بازگشت