Title :
Estimation of flashover rates of overhead power distribution lines by lightning strokes to nearby ground
Author_Institution :
Center for Electr. Power, Tennessee Technol. Univ., Cookeville, TN, USA
fDate :
7/1/1989 12:00:00 AM
Abstract :
A method is proposed for calculating the flashover of an overhead power distribution line caused by lightning strokes to nearby ground. The results are presented in the form of a graph of flashover rate vs. BIL (basic impulse insulation level) for a 10 m high line and ground flash density of 10/km2/year. Flashover rates of lines of different heights and ground flash densities can be estimated from this graph
Keywords :
flashover; lightning; power overhead lines; basic impulse insulation level; flashover rates; ground flash densities; lightning strokes; overhead power distribution lines; Clouds; Electrostatics; Flashover; Lightning; Magnetic fields; Power distribution; Power distribution lines; Power system reliability; Statistical distributions; Voltage;
Journal_Title :
Power Delivery, IEEE Transactions on