Title : 
Performance of Insulators Covered With Snow or Ice
         
        
            Author : 
Fujimura, Tetsuo ; Naito, Katsuhiko ; Hasegawa, Yoshio ; Kawaguchi, Toshiyuki
         
        
            Author_Institution : 
NGK INSULATORS, LTD.
         
        
        
        
        
        
            Abstract : 
This paper describes the results of investigation made into the performance of insulators covered with snow or ice. The AC and DC withstand voltages of snow-covered insulators were characterized by the conductivity of water melted from the snow. The AC withstand voltage of ice-coated insulators was characterized by the length of icicles and conductivity of the water melted from the ice. And the switching impulse flashover voltage of snow-covered insulator strings was almost proportional to gap length between the arcing horns or the insulator strings. Flashover voltage of a 75% snow-covered insulator string, which means the worst case, was 40 ¿65% of the positive wet flashover voltage of the clean insulator string.
         
        
            Keywords : 
Contamination; Flashover; Ice; Impulse testing; Insulation; Insulator testing; Life testing; Power transmission lines; Snow; Voltage;
         
        
        
            Journal_Title : 
Power Apparatus and Systems, IEEE Transactions on
         
        
        
        
        
            DOI : 
10.1109/TPAS.1979.319479