DocumentCode :
1185719
Title :
A Novel Adaptive PMU Based Transmission Line Relay: Design and EMTP Simulation Results
Author :
Jiang, J. A. ; Liu, C. W. ; Chen, C. S.
Author_Institution :
National Taiwan University, Taipei, Taiwan
Volume :
22
Issue :
7
fYear :
2002
fDate :
7/1/2002 12:00:00 AM
Firstpage :
61
Lastpage :
61
Abstract :
This paper proposes a novel adaptive relaying scheme based on Phasor Measurement Units (PMUs) for transmission lines. The proposed adaptive relaying scheme can provide an extremely accurate discrimination between in-zone and out-of-zone faults. Two novel and composite fault discrimination indices in terms of Clarke components of synchronized voltage and current phasors at two ends of a line are derived. A line parameter estimation algorithm is developed and built in the new designed relay to solve the uncertainty problem of line parameters. The proposed relaying scheme is independent of fault types, fault locations, fault path resistance, fault inception angles, and the variations of source impedance. The tripping decision time of the designed relay is very fast and is almost held well within 6 milliseconds for most fault events. All the EMTP simulation results show that the proposed adaptive relaying scheme provides a high level of dependability and security.
Keywords :
Algorithm design and analysis; EMTP; Fault location; Impedance; Parameter estimation; Phasor measurement units; Relays; Transmission lines; Uncertainty; Voltage; Adaptive relaying; global positioning system (GPS); line relaying; phasor measurement unit (PMU);
fLanguage :
English
Journal_Title :
Power Engineering Review, IEEE
Publisher :
ieee
ISSN :
0272-1724
Type :
jour
DOI :
10.1109/MPER.2002.4312421
Filename :
4312421
Link To Document :
بازگشت