DocumentCode :
1185728
Title :
Diagnostic Methods in Revealing Internal Moisture in Polymer Housed Metal Oxide Surge Arresters
Author :
Lahti, K. ; Kannus, K. ; Nousianen, K.
Author_Institution :
Tampere University of Technology
Volume :
22
Issue :
7
fYear :
2002
fDate :
7/1/2002 12:00:00 AM
Firstpage :
61
Lastpage :
61
Abstract :
Diagnostic measurements performed for surge arresters are normally studied by evaluating their suitability to detect ageing and degradation of metal oxide material. The suitability of different methods for revealing intemal moisture in arresters has not been studied much. This aspect is considered in the paper based on measurement results obtained during a 1.5 year laboratory test series conducted for six different types of polymer housed distribution class arresters. AC power losses, third harmonic content of resistive leakage current, DC leakage current and partial discharge measurement results over the test period are given and discussed. Details of the measurement procedures suitable for measuring polymeric arresters with intemal moisture are also studied. AC power loss and DC leakage current measurements were found to be good methods, while the other two can only be used as additional methods when diagnosing intemal moisture in polymer housed arresters.
Keywords :
Aging; Arresters; Degradation; Leakage current; Moisture measurement; Partial discharge measurement; Performance evaluation; Polymers; Surges; Testing; Arresters; degradation; insulation; leak detection; moisture; partial discharges; polymers;
fLanguage :
English
Journal_Title :
Power Engineering Review, IEEE
Publisher :
ieee
ISSN :
0272-1724
Type :
jour
DOI :
10.1109/MPER.2002.4312422
Filename :
4312422
Link To Document :
بازگشت