DocumentCode
1185790
Title
A High Speed, Discriminating Generator Loss of Excitation Protection
Author
Lee, D.C. ; Kundur, P. ; Brown, R.D.
Author_Institution
Ontario Hydro
Issue
6
fYear
1979
Firstpage
1895
Lastpage
1899
Abstract
A new loss of excitation protection scheme has been devised in order to minimize the system voltage disturbance caused by excitation failure. It was designed specifically to prevent tripping of a sensitive load adjacent to a generating station with only one unit in operation. Besides meeting the special requirements of the single unit environment, the scheme appears to have some advantage over conventional loss-of-field protection when used in a station with more than one unit in service. The relay described has been in service for two years, complementing conventional protection, at a large nuclear plant which now has three units in operation. The relay is being modified to include limited over-excitation protection for future applications.
Keywords
Chemicals; Nuclear power generation; Power & Energy Society; Power generation; Power system protection; Power system stability; Power system transients; Protective relaying; Regulators; Voltage;
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/TPAS.1979.319368
Filename
4113705