DocumentCode :
1185839
Title :
The Corona and Radio Interference Performance of the Nelson River HVDC Transmission Lines
Author :
Morris, R.M. ; Morse, A.R. ; Griffin, J.P. ; Norris-Elye, O.C. ; Thio, C.V. ; Goodman, J.S.
Author_Institution :
National Research Council of Canada,
Issue :
6
fYear :
1979
Firstpage :
1924
Lastpage :
1936
Abstract :
Prior to construction of the Manitoba Hydro Nelson River DC system, the HVDC corona performance of the transmission lines was predicted from test line measurements made at NRC Ottawa in 1967-69. Radio interference, corona power loss and the effect of drag stringing were studied [1,2]. Since completion of the two 895 km (556 mile) lines in Manitoba in March 1971, radio interference measurements were made at various system voltages. This paper gives radio interference results and compares them with test line predictions. Measurements of combined corona and insulator leakage loss on the 895 km line were made also in April 1978. The results of loss tests are presented and compared with 1967-69 predictions.
Keywords :
Corona; Electromagnetic interference; HVDC transmission; Insulation; Loss measurement; Power transmission lines; Rivers; System testing; Transmission line measurements; Voltage;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9510
Type :
jour
DOI :
10.1109/TPAS.1979.319372
Filename :
4113709
Link To Document :
بازگشت