Abstract :
This work presents the steady-state performance of a metering-type current transformer used in circuits with asymmetrically triggered silicon-controlled rectifiers or triacs. It was found that minute differences between the triggering angles generate sufficient dc bias of the magnetic core to impair the accuracy of the transformer.
Keywords :
Circuit testing; Current measurement; Current transformers; DC generators; Phase measurement; Potentiometers; Shape; Steady-state; Thyristors; Voltage;